Conference Paper: Application of underfloor ventilation system some design considerations

TitleApplication of underfloor ventilation system some design considerations
Authors
KeywordsThermal comfort
Underfloor ventilation
Predicted mean vote
Age of air
Issue Date2003
Citation
Proceedings of the 2003 4th International Symposium on Heating, Ventilating and Air Conditioning, 2003, p. 354-361 How to Cite?
AbstractThis paper describes a series of experiments, which investigated the performances of the underfloor ventilation systems in thermal comfort and indoor air quality aspects. Both the floor return (FR) and the top return (TR) types were tested. An additional set of experiments were conducted on the traditional ceiling-based system for comparison. Results reveal that the underfloor systems created significant overcooling in the nearby area of the floor supply terminals and temperature stratifications in the room. The underfloor systems achieved some level of improvements in ventilation performance. The FR system exhibited a more localized ventilation characteristic than that of the TR system. With the support from the experimental results, some design considerations were suggested for the underfloor ventilation systems.
Persistent Identifierhttp://hdl.handle.net/10722/255894

 

DC FieldValueLanguage
dc.contributor.authorHu, J. S.-
dc.contributor.authorWan, M. P.-
dc.contributor.authorChao, Christopher Y.-
dc.contributor.authorLaw, Anthony-
dc.date.accessioned2018-07-16T06:13:59Z-
dc.date.available2018-07-16T06:13:59Z-
dc.date.issued2003-
dc.identifier.citationProceedings of the 2003 4th International Symposium on Heating, Ventilating and Air Conditioning, 2003, p. 354-361-
dc.identifier.urihttp://hdl.handle.net/10722/255894-
dc.description.abstractThis paper describes a series of experiments, which investigated the performances of the underfloor ventilation systems in thermal comfort and indoor air quality aspects. Both the floor return (FR) and the top return (TR) types were tested. An additional set of experiments were conducted on the traditional ceiling-based system for comparison. Results reveal that the underfloor systems created significant overcooling in the nearby area of the floor supply terminals and temperature stratifications in the room. The underfloor systems achieved some level of improvements in ventilation performance. The FR system exhibited a more localized ventilation characteristic than that of the TR system. With the support from the experimental results, some design considerations were suggested for the underfloor ventilation systems.-
dc.languageeng-
dc.relation.ispartofProceedings of the 2003 4th International Symposium on Heating, Ventilating and Air Conditioning-
dc.subjectThermal comfort-
dc.subjectUnderfloor ventilation-
dc.subjectPredicted mean vote-
dc.subjectAge of air-
dc.titleApplication of underfloor ventilation system some design considerations-
dc.typeConference_Paper-
dc.description.naturelink_to_subscribed_fulltext-
dc.identifier.scopuseid_2-s2.0-4444260263-
dc.identifier.spage354-
dc.identifier.epage361-